Metal Stud Framing For Combination Fire Smoke Dampers
This video has two parts with openings 36 x 36 and under, followed by openings with any dimension over 36. INSTRUCTIONS 1. Frame wall openings as shown. 2. Double vertical studs are not required for openings 36 w x 36 h (914 x 914) or smaller. 3. All construction and fasteners must meet the requirements of the appropriate wall design and, or local codes. 4. Consult the authority having jurisdiction for other acceptable framing methods. NOTE: The Metal Stud Construction figures depict mounting plates installed on both sides of the partition. A single cinch plate may be sufficient. Refer to the instructions for single angle installation requirements. For more info:
|
|